DSX Access Systems, Inc.

 

 

Input Types

 

Two, Three, and Four State Inputs

 

 

Systems using WinDSX support two, three, and four state supervised input monitoring. There are five programmable circuit types, which are shown below. Two and three state inputs use a 1K-ohm resistor. Four state inputs utilize a 180-ohm and 820-ohm resistor each. All inputs can be individually programmed for any one of the five circuit types. Three and Four State inputs support trouble conditions.

 

Note /// Input Circuit Types: 0 = 2 States, Type 1 & 2 = 3 States, Type 3 & 4 = 4 States.

Note /// These Input Circuit Types apply to all Controllers except the DSX-1043.