DSX Access Systems, Inc. |
Standby
![]()
|
Current Draw Worksheet |
|
|||||||||
|
|
||||||||||
|
Enter
quantity of each item to calculate an approximate total current draw. |
|
|||||||||
|
|
||||||||||
|
|
|
|
|
Current Draw(A) |
|
Quantity |
|
Total |
|
|
|
DSX
Product |
DSX-1040CDM |
0.04 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-1042 |
0.3 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-1043 |
0.8 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-1044 |
0.55 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-FRB8 |
0.24 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-MCI |
0.03 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-1035 |
0.5 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-232-MUX |
0.1 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-485T |
0.03 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-220 |
0.21 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-400IB |
0.05 |
x |
0 |
= |
0 |
|
|||
|
|
SPI-1442-FI |
0.5 |
x |
0 |
= |
0 |
|
|||
|
|
DSX-TDM |
0.16 |
x |
0 |
= |
0 |
|
|||
|
|
|
|
|
|
|
|
||||
|
Readers |
|
W-S/W-T/W-K |
0.04 |
x |
0 |
= |
0 |
|
||
|
|
W-SPIN |
0.14 |
x |
0 |
= |
0 |
|
|||
|
|
|
|
|
|
|
|
||||
|
|
ID-PL6005 |
0.075 |
x |
0 |
= |
0 |
|
|||
|
|
ID-MP5365 |
0.11 |
x |
0 |
= |
0 |
|
|||
|
|
ID-TL5395 |
0.115 |
x |
0 |
= |
0 |
|
|||
|
|
ID-PR6030 |
0.12 |
x |
0 |
= |
0 |
|
|||
|
|
ID-PR5355 |
0.12 |
x |
0 |
= |
0 |
|
|||
|
|
ID-PR5455 |
0.125 |
x |
0 |
= |
0 |
|
|||
|
|
ID-PK5355 |
0.12 |
x |
0 |
= |
0 |
|
|||
|
|
|
|
|
|
|
|
||||
|
|
FP4551A |
0.086 |
x |
0 |
= |
0 |
|
|||
|
|
ASR-501 |
0.091 |
x |
0 |
= |
0 |
|
|||
|
|
FP3511A/FP3517A |
0.086 |
x |
0 |
= |
0 |
|
|||
|
|
FP3521A/FP3527A |
0.086 |
x |
0 |
= |
0 |
|
|||
|
|
FP3231A/FP3237A |
0.117 |
x |
0 |
= |
0 |
|
|||
|
|
|
|
|
|
|
|
|
|||
|
|
MR-10 |
0.02 |
x |
0 |
= |
0 |
|
|||
|
|
MR-20/BR-20 |
0.08 |
x |
0 |
= |
0 |
|
|||
|
|
|
|
|
|
|
|
||||
|
|
D-544/D-644 |
0.035 |
x |
0 |
= |
0 |
|
|||
|
|
D-584 |
0.045 |
x |
0 |
= |
0 |
|
|||
|
|
D-740 |
0.045 |
x |
0 |
= |
0 |
|
|||
|
|
D-780 |
0.055 |
x |
0 |
= |
0 |
|
|||
|
|
|
|
|
|
|
|
||||
|
|
TKS-110 |
0.05 |
x |
0 |
= |
0 |
|
|||
|
|
SK-028/SK-034/SK-038 |
0.135 |
x |
0 |
= |
0 |
|
|||
|
|
DS-12 |
0.02 |
x |
0 |
= |
0 |
|
|||
|
|
|
|
|
|
|
|
|
|||
|
Miscellaneous |
|
0 |
x |
0 |
= |
0 |
|
|||
|
|
|
0 |
x |
0 |
= |
0 |
|
|||
|
|
|
0 |
x |
0 |
= |
0 |
|
|||
|
|
||||||||||
|
|
|
Total Current Draw |
|
0 |
Amps |
|
||||
|
|
(Use
chart below to determine required AH) |
|
||||||||
|
|
||||||||||
|
|
||||||||||
|
If your
value falls between 2 points, use the next higher value. |
|
|||||||||
|
Divide
the determined Amp Hour requirement by 7 (and round up) to get the number of
7AH batteries you need. |
|
|||||||||
|
|
||||||||||
|
|
|
|
Backup
Time (Hrs) |
|
||||||
|
|
|
1 |
2 |
4 |
6 |
8 |
10 |
20 |
|
|
|
Current Draw (A) |
1 |
2 |
3 |
5 |
8 |
10 |
12 |
20 |
|
|
|
2 |
4.5 |
7 |
10 |
18 |
18 |
26 |
40 |
|
||
|
3 |
7 |
10 |
18 |
26 |
33 |
33 |
60 |
|
||
|
4 |
7 |
12 |
20 |
33 |
40 |
55 |
80 |
|
||
|
5 |
10 |
18 |
26 |
40 |
55 |
55 |
100 |
|
||
|
6 |
12 |
18 |
33 |
55 |
55 |
75 |
na |
|
||
|
7 |
12 |
26 |
40 |
55 |
75 |
80 |
na |
|
||
|
8 |
18 |
26 |
40 |
60 |
75 |
100 |
na |
|
||
|
|
|
|
|
|||||||
|
|
|
|
Required