At least one Back-up Battery is required for each DSX Controller and Package and is charged by the Controller or PDM trickle charge circuit. It supplies back up power to the DSX Controller, Modem, LAN Module (if attached), Card Readers, and Keypads.

 

The panel’s charging circuit can support multiple 12V 7AH batteries. The Controllers have a battery fuse for overload or reverse polarity protection and a Blown-Fuse LED Indicator. The DSX panel or PDM monitors for Low Battery turning on a LED Indicator and reporting the status to the PC (1022) or activating a relay output that can be tied to an input (1040 PDM).

 

Batteries are tested, automatically, once a day at 10:00AM by the DSX-1020, 1022 and set to test anytime on the 1040 Series Controllers.

 